Buffer Tank

Specifications

A buffer tank is a storage tank used on the cold user side of an air-conditioning system.
The tank is used as storage to cover peak loads or in situations when a surge in demand exceeds the capacity of the cooling system.

Chillers are designed to operate with a minimum water volume, which typically ranges from 22 litre to 38 litres per ton for air conditioning application, for to get better temperature accuracy.

Most of the chiller compressors can only start 3 to 4 times per hour. If the compressor is off and if there is a demand for chilled water the compressor cannot get on immediately. Without chilled water, building will not get the required cooling. To solve this problem chilled water buffer vessels are added in the system. These tanks increase the capacity of the chilled water in the system and stabilize the return.
Tank manufactured as per ASME Standard Sec VIII Division
Ring supports
Internal Baffle
Air vent
Insulation and cladding (optional)
Flanged connection (inlet and outlet)
Manhole (optional)

Tank will be externally sandblasted to SA 2.5 and then coated with two coats of red oxide primer.
Horizontal configuration also available. Manufacturers data report for pressure vessels from U-1A as required by the provisions of ASME code will be furnished for each chilled water buffer tank. Standard working pressure 10 bar, Test pressure 15 bar.

Features

  • Chilled Water Buffer Tanks
    Internal Baffle Helps Properly Circulate Water.
  • Available up to 200 ltr 5000 ltr
    Connections from 3″ to 12″.
    Max. Working Pressure: 125 or 150 PSIG.
    Max. Operating Temperature: 450° F.
    Seismic Restraints, Sensor Ports and Grooved Pipe Connections Available.
  • Hot Water Buffer Tanks
    2-Port Tanks Add System Mass.
    4-Port Tanks Add System Mass and Hydraulic Separation.
  • Available up to 1500ltr
    Connections: 2″, 3″ and 4″
    Max. Working Pressure: 125 or 150 PSIG.
    Max. Operating Temperature: 450° F.
    Seismic Restraints, Sensor Ports and Grooved Pipe Connections Available.